Series VIT-AFSBY distribution boards are equipped with an isolation transformer as well as with a changeover and monitoring module including all necessary monitoring components as to DIN VDE 100-710 for IT systems:
The secondary side of the isolation transformer is equipped with at least 6 two-pole circuit breakers. Group 2 sockets are being connected to these.
In order to reduce or avoid noise disturbance by air circulating fans, waste heat is conducted by free convection.
Series VIT-AFSBY distribution boards are equipped with an isolation transformer as well as with a changeover and monitoring module including all necessary monitoring components as to DIN VDE 100-710 for IT systems:
The secondary side of the isolation transformer is equipped with at least 6 two-pole circuit breakers. Group 2 sockets are being connected to these.
In order to reduce or avoid noise disturbance by air circulating fans, waste heat is conducted by free convection.
Type | Power | Weight | Loss* |
---|---|---|---|
VIT-AFSBY-112S- | 5000VA | ca.145kg | ca. 200W |
VIT-AFSBY-112S- | 6300VA | ca.150kg | ca. 210W |
VIT-AFSBY-112S- | 8000VA | ca.160kg | ca. 230W |
VIT-AFSBY-114S- | 5000VA | ca.155kg | ca. 200W |
VIT-AFSBY-114S- | 6300VA | ca.160kg | ca. 210W |
VIT-AFSBY-114S- | 8000VA | ca.170kg | ca. 230W |
* Specification for energy efficient „Green Line“ Transformers.
Basic types
VIT-A | Number of circuits | Drawing No. | Art No. |
---|---|---|---|
-112S-xxxx- | 12 | 9700089 | B101944** |
-114S-xxxx- | 12 | 9700090 | B101945** |
-114S-xxxx- | 18 | 9700091 | B101946** |
-114S-xxxx- | 24 | 9700092 | B101947** |
** Without transformer, the required power must be specified.
Other versions on request.