ISOMETER® IR423

  • Ground-fault monitoring device for mobile generators
  • Protective separation with ground-fault monitoring and disconnection
  • According to IEC 60364-5-55 and IEC 61557-8
  • Two separately configurable response values
  • Multi-functional LC display

The ISOMETER® of the IR423 series is designed to monitor the insulation resistance RF of an ungrounded AC system of 0…300 V to earth that is supplied by a mobile generator accor­ding to IEC 60364-5-551 / DIN VDE 0100-551 (VDE 0100-551). The IR423 is suitable for AC sys­tems with operating frequencies ≥ 30 Hz as well as for AC systems with directly connected DC circuits. The maximum permissible system leakage capacitance Cemax is 5 F.

Questions? Contact us!

ISOMETER® IR423
ISOMETER® IR423
  • Ground-fault monitoring device for mobile generators
  • Protective separation with ground-fault monitoring and disconnection
  • According to IEC 60364-5-55 and IEC 61557-8
  • Two separately configurable response values
  • Multi-functional LC display

The ISOMETER® of the IR423 series is designed to monitor the insulation resistance RF of an ungrounded AC system of 0…300 V to earth that is supplied by a mobile generator accor­ding to IEC 60364-5-551 / DIN VDE 0100-551 (VDE 0100-551). The IR423 is suitable for AC sys­tems with operating frequencies ≥ 30 Hz as well as for AC systems with directly connected DC circuits. The maximum permissible system leakage capacitance Cemax is 5 F.

Questions? Contact us!

Features

  • Insulation monitoring for mobile generators AC 0…300 V
  • Protection by electrical separation with insulation monitoring and disconnection
  • Version “W” for protection against high mechanical stress
  • Two separately adjustable response values
  • Connection monitoring system/earth
  • Power On LED, alarm LEDs: Alarm 1, Alarm 2
  • Internal/external test/reset button
  • Two separate alarm relays (one changeover contact each)
  • N/O or N/C operation, selectable
  • Fault memory behaviour, selectable
  • Self monitoring with automatic alarm
  • Multi-functional LC display
  • Adjustable response delay
  • Two-module enclosure (36 mm)
  • Push-wire terminal (two terminals per connection)

Applications

  • IEC 60364-7-717, DIN VDE 0100-717 (2005) Electrical installations in mobile or transportable units
  • DIN VDE 0100-551 (VDE 0100-551), IEC 60364-5-551 Low-voltage generating sets (mobile generators)
  • GW 308 “Mobile Stromerzeuger für Rohrleitungsbaustellen 8/00” (Mobile auxiliary power generators on pipeline site”) (DVGW)
  • BGI 867 (German Berufsgenossenschaft Information) Auswahl und Betrieb von Ersatzstromerzeugern auf Bau- und Montagestellen (Selecting and operating standby generators on construction and installation sites)

ISOMETER® IR423 Variant(s)

TypeNominal system voltage* UnSupply voltage* USArt. No.**
IR423D4-1AC 0…300 V, 30…460 HzAC 16…72 V, 30…460 Hz / DC 9,6…94 VB71016304
B91016304
IR423D4-2AC 0…300 V, 30…460 HzAC/DC 70…300 V, 30…460 HzB71016305
B91016305
IR423-D4W-1AC 0…300 V, 30…460 HzDC 9,6…94 V / AC 16…72 V, 30…460 HzB71016304W
B91016304W
IR423-D4W-2AC 0…300 V, 30…460 HzAC/DC 70…300 V, 30…460 HzB71016305W
B91016305W

* absolute values
**(B7… = push-wire terminal / B9… = screw-type terminal)

Optional Accessories for ISOMETER® IR423

TypeArt. No.
Mounting clip for screw mounting (one piece per device)B98060008
Mounting frame XM420B990994 

Downloads for ISOMETER® IR423

NameCategorySizeLanguageTimestampD-/B-Number
UKCA - IR42x Declarations of Conformity 177.1 KB 2024/12/1010.12.2024
RoHS/REACH Report - B71016304 RoHS/REACH Report 252.5 KB 2024/09/0606.09.2024
IR42x CE Declarations of Conformity 105.3 KB 2024/12/1313.12.2024
IR423 Manuals 2.3 MB EN2024/09/2727.09.2024D00038
IR423 Datasheets 577.1 KB EN2024/12/1818.12.2024D00038
Changed variants of relays from goldplated to silver-plated contacts Technical Information 166.3 KB EN2022/06/2727.06.2022