The ground-fault locators ISOSCAN® EDS44x are used in connection with the ISOMETER® iso685-D-P or the locating current injector PGH to locate ground faults in ungrounded power supply systems (IT systems).
They detect locating current signals generated by the ground-fault monitoring device iso685-D-P or IRDH575 or the locating current injector PGH and evaluate them correspondingly. Up to 12 measuring current transformers can be connected to an EDS44x. In total, up to 21 ground-fault locators can be connected via an RS-485 interface (BS bus protocol) and thereby up to 252 outgoing circuits can be monitored.
The ground-fault locators ISOSCAN® EDS44x are used in connection with the ISOMETER® iso685-D-P or the locating current injector PGH to locate ground faults in ungrounded power supply systems (IT systems).
They detect locating current signals generated by the ground-fault monitoring device iso685-D-P or IRDH575 or the locating current injector PGH and evaluate them correspondingly. Up to 12 measuring current transformers can be connected to an EDS44x. In total, up to 21 ground-fault locators can be connected via an RS-485 interface (BS bus protocol) and thereby up to 252 outgoing circuits can be monitored.
Type | Supply voltage US* | Response value | Art. no. |
---|---|---|---|
EDS441-S | AC/DC 24…240 V | 0.2…1 mA | B91080204 |
EDS441-L-4 | AC/DC 24…240 V | 0.2…1 mA | B91080205 |
EDS441-LAB-4 | AC/DC 24…240 V | 0.2…1 mA | B91080207 |
*Absolute values
Accessories
Type | Supply voltage US | Art. no. |
---|---|---|
DI-1PSM (RS-485 repeater) | AC/DC 24 V ± 20 % | B95012044 |
DI-2USB (interface converter RS-485/USB) with USB cable | Supplied by USB interface | B95012045 |
IOM441-S (Input/Output module) | 12-fold relay module | B95012057 |
Measuring current transformer for EDS441
Type | Internal diameter/mm | Design type | Art. no. |
---|---|---|---|
CTAC20/1 | 20 | circular | B98110006 |
CTAC35/1 | 35 | circular | B98110008 |
Alternative measuring current transformer from the Bender program
Type | Internal diameter/mm | Design type | Art. no. |
---|---|---|---|
W10/8000 | 10 | circular | B911759 |
W1-35/8000 | 35 | circular | B911756 |
W10/8000-6 | 10 | circular, 6-fold | B911900 |
WS20x30/8000 | 20 x 30 | split-core | B911764 |
WS50x80/8000 | 50 x 80 | split-core | B911757 |
Measuring current transformer for EDS441-LAB
Type | Internal diameter/mm | Design type | Art. no. |
---|---|---|---|
CTUB104-CTB20P | 20 | circular | B78120033 |
CTUB104-CTB35P | 35 | circular | B78120034 |
CTUB104-CTB60P | 60 | circular | B78120035 |
Name | Category | Size | Language | Timestamp | D-/B-Number |
---|---|---|---|---|---|
TÜV NORD - AGH150x, CTACx, CTBCx, EDS44x, CTUB10x, MRCDB30x und RCMB30x | Certificates | 428.8 KB | DE | 2023/10/1111.10.2023 | |
TÜV NORD - AGH150x, CTACx, CTBCx, EDS44x, CTUB10x, MRCDB30x and RCMB30x | Certificates | 408.6 KB | EN | 2023/10/1111.10.2023 | |
EDS44x | CE Declarations of Conformity | 88.3 KB | 2022/08/1212.08.2022 | ||
EDS440/EDS441 | Quickstarts | 872.2 KB | EN | 2024/09/1818.09.2024 | D00201 |
EDS440/EDS441 | Manuals | 13.1 MB | EN | 2024/09/0505.09.2024 | D00201 |
EDS440/EDS441 | Datasheets | 8.2 MB | EN | 2024/09/1818.09.2024 | D00201 |
EDS440/EDS441 - Modbus settings | Manuals | 189.8 KB | EN | 2020/01/1414.01.2020 | D00201 |
EDS441-LNA-KITS Datasheet (US) | Datasheets | 4.7 MB | EN | 2024/02/2727.02.2024 | D00201 |
Industrial EDS | Flyers | 1.1 MB | EN | 2021/04/2828.04.2021 | |
Healthcare EDS | Flyers | 1.7 MB | EN | 2021/04/2929.04.2021 |